General Specifications |
Function |
Nickel concentration, pH, temperature monitor and control for electroless Nickel plating process |
Model |
P7228 |
Installation |
Freestanding Type |
Housing |
IP65 |
Dimensions |
H1250* W550* D430mm |
Range |
Ni+:0-10 g/L, pH: 0-14, Temperature: 0-100ºC |
Accuracy |
Ni+: <±0.5 % of F.S. Range, pH:±0.01, Temperature:±0.2ºC |
Resolution |
Ni: 0.01g/L, pH: 0.01, Temperature: 0.1ºC |
Response Time |
Real time and continuous monitoring |
Data Log |
Simultaneously display parameters of Nickel, pH, temperature, and analysis status, nickel usage cycle, nickel adding volumes. |
Pump control |
Up to 5 chemical dosing pumps and 1 sampling pump |
Auto-dosing |
5 connection points for the supplement for Nickel dosages and pH solutions |
Shutdown Alarm |
Abnormal detection of concentration, pH value, and temperature (adjustable of high and low-point) |
Light source/ detector |
Special LED with approx. 3 years of life span. Photodiode |
Calibration |
Automatic calibration. Can switch to manual calibration, high- and low- point |
Principle |
24-bit high-resolution A/D converter; high integrated SMD Technology, 24-bit AD-Converting. Signal filtration, simulation of the stability of wiring |
Display |
10” LCD color touch panel display |
Self-Diagnosis |
The system is continuously self-diagnosis. The error management helps to identify problems. (Display errors and save historical data) |
Sample Conditions |
• Sample temperature: a condensation device is equipped to cool down the sample and control temperature under 40 °C • Sample flow: Continuous, 25 to 230 ml/min • Sample connection: use external pump connect with 4.75mm Teflon tube • Suspended solids: 200 microns or less |
Environmental Conditions |
• Ambient operating temperature: 0 – 40 °C • Ambient operating humidity: Up to 95 % RH non-condensing |
Electrical Conditions |
Power supply ranges:115 / 230 VAC, 50 / 60 Hz,<500 Watt |
Analog Outputs |
1 isolated current output, 4-20mA range. With the option of RS485 |
Alarms / Relay outputs |
8 relays: • 1 sampling control relay • 1 analysis alarm relay • 1 failure alarm relay • 5 connection points for fully user-assignable relays |